ASTM-D2759 Standard Practice for Sampling Gas from a Transformer Under Positive Pressure

ASTM-D2759 - 2000 R17 EDITION - CURRENT
Show Complete Document History

Document Center Inc. is an authorized dealer of ASTM standards.
The following bibliographic material is provided to assist you with your purchasing decision:

Standard Practice for Sampling Gas from a Transformer Under Positive Pressure
ORDER

Price:

$55.00        


Want this as a site license?

Scope

1.1 This practice covers the sampling of gas above the insulating liquid of a transformer. A gas sampling bottle collects the gas sample from the gas space that is at a positive pressure.

1.2 Representative samples of gas are taken for analysis to determine their compositions.

1.3 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.

1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.

1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

Significance and Use

2.1 A gas sample from above the insulating liquid in transformers and other electrical power apparatus can be used to give an early indication of developing fault conditions. Combustible gases are formed from the breakdown of the insulating materials under thermal and electrical stress. Excessive concentrations of combustible gases indicate the need to take appropriate action.

2.2 It is important that gas samples from equipment be taken from the gas space directly above the liquid level, and not from remote expansion compartments, such as tank bracing bands.

2.3 The procedure described should be carefully followed to ensure that the sample is not diluted by air or nitrogen, or contaminated by residual materials in the sampling bottle.

Keywords

gas; positive pressure; sampling gas; transformer ;; ICS Number Code 29.180 (Transformers. Reactors)

To find similar documents by ASTM Volume:

10.03 (Electrical Insulating Liquids and Gases; Electrical Protective Equipment)

To find similar documents by classification:

29.180 (Transformers. Reactors Instrument transformers, see 17.220.20)

This document comes with our free Notification Service, good for the life of the document.

This document is available in either Paper or PDF format.

Document Number

ASTM-D2759-00(2017)

Revision Level

2000 R17 EDITION

Status

Current

Modification Type

Reapproval

Publication Date

Oct. 15, 2017

Document Type

Practice

Page Count

2 pages

Committee Number

D27.07