Standard Specification for 19 Wire Combination Unilay-Stranded Copper Conductors for Subsequent Insulation
The following bibliographic material is provided to assist you with your purchasing decision:
Scope
1.1 This specification covers bare combination unilay-stranded conductors made from round copper wires, either uncoated or coated with tin or lead alloy for insulated conductors for electrical purposes. These conductors shall be constructed with a central core wire surrounded by two layers of helically laid wires, resulting in an outer diameter equal to the compressed-stranded equivalent conductor. (See Explanatory Note 1 and Note 2).
Note 1—For the purpose of this specification, combination unilay conductor is defined as follows: a central core wire surrounded by a layer of six helically laid wires of the same diameter as the core wire with a helically laid outer layer containing six smaller wires alternated between six wires of the same diameter as the wires in the layer underneath. Both layers have a common length and direction of lay (see Fig 1).
1.2 For the purpose of this specification, normal conductor classification (Class AA, A, B, C) is not applicable as these conductors are intended for subsequent insulation. The descriptive term combination unilay-stranded shall be used in place of conductor classification.
1.3 The values stated in inch-pound or SI units are to be regarded separately as standard. Each system shall be used independently of the other. Combining values from the two systems may result in nonconformance with the specification. For conductor sizes designated by AWG or kcmil, the requirements in SI units have been numerically converted from corresponding values, stated or derived, in inch-pound units. For conductor sizes designated by SI units only, the requirements are stated or derived in SI units.
1.3.1 For density, resistivity, and temperature, the values stated in SI units are to be regarded as standard.
Keywords
copper electrical conductors-stranded; electrical performance; insulated wire and cable-insulation; mechanical testing; rated strength (electrical conductor wire); strength-general; unilay-stranded copper electrical conductors; nineteen wire unilay-stranded copper conductors (for subsequent; insulation); ICS Number Code 29.060.20 (Cables)
To find similar documents by ASTM Volume:
To find similar documents by classification:
This document comes with our free Notification Service, good for the life of the document.
This document is available in either Paper or PDF format.
Document Number
ASTM-B0787_B0787M-04R20
Revision Level
2004 R20 EDITION
Status
Current
Modification Type
Revision
Publication Date
Jan. 1, 2020
Document Type
Specification
Page Count
6 pages
Committee Number
B01.04